為什么在FM350-1中選24V編碼器,啟動(dòng)以后,SF燈常亮,FM350-1不能工作?
要檢查一下,首先在軟件組態(tài)中要選擇編碼器類型(為24V),再檢查一下,FM350-1側(cè)面的跳線開關(guān),因?yàn)槿笔〉拈_關(guān)設(shè)置為5V編碼器,一般用戶沒有設(shè)置,開機(jī)后,SF燈就會(huì)常亮。另外,還可以看看在線硬件診斷,可以看看錯(cuò)誤產(chǎn)生的原因,是否模板壞了。

62: FM350">

小视频免费在线观看_夜夜b_男女隐私免费视频_国产一级性生活视频_久久综合入口_精品国内视频

技術(shù)頻道

西門子S7-300 編程多個(gè)問題解答之四(61-80)

為什么在FM350-1中選24V編碼器,啟動(dòng)以后,SF燈常亮,FM350-1不能工作?
要檢查一下,首先在軟件組態(tài)中要選擇編碼器類型(為24V),再檢查一下,FM350-1側(cè)面的跳線開關(guān),因?yàn)槿笔〉拈_關(guān)設(shè)置為5V編碼器,一般用戶沒有設(shè)置,開機(jī)后,SF燈就會(huì)常亮。另外,還可以看看在線硬件診斷,可以看看錯(cuò)誤產(chǎn)生的原因,是否模板壞了。

62: FM350-1的鎖存功能是否能產(chǎn)生過程中斷?
FM350-1的鎖存功能是不能產(chǎn)生過程中斷,但是可以產(chǎn)生過零中斷。
FM350-1的裝載值必須為零,隨者鎖存功能的執(zhí)行(DI的上升沿開始),當(dāng)前的計(jì)數(shù)值被儲(chǔ)存到另一地址然后置為初始值零,產(chǎn)生過零中斷,在OB40中可以讀出中斷并相應(yīng)的鎖存值。鎖存值也可以從FM350-1的硬件組態(tài)地址的前4個(gè)字節(jié)中讀出。

63:在FM350-1中,怎樣觸發(fā)一個(gè)比較器輸出?
FM350-1中自帶的輸出點(diǎn)具有快速性、實(shí)時(shí)性,不必要經(jīng)過CPU的映像區(qū)處理。輸出點(diǎn)一般對(duì)應(yīng)于比較器,首先在硬件組態(tài)中定義比較器輸出類型,如:輸出值為1或?yàn)槊}沖輸出,然后在程序中設(shè)置比較值。在FM350-1中,地址在通訊DB(UDT生成)塊中為18(比較值1)、22(比較值2),類型為DINT,然后激活輸出點(diǎn)28.0(DQ0)、28.1(DQ1),這樣比較器就可以工作了。

64:在FM350-2中,工作號(hào)的作用是什么?
工作號(hào)是S7-300CPU與FM進(jìn)行通訊的任務(wù)號(hào),每次的交換數(shù)據(jù)只是部分?jǐn)?shù)據(jù)交換,而非全部數(shù)據(jù),這樣可以減少FM的工作負(fù)載,工作號(hào)又分寫工作號(hào)和讀工作號(hào),例如在FM350-2中指定DB1為通訊數(shù)據(jù)塊,如果把寫工作號(hào)12寫入到DB1.DBB0中,把200寫入到DB1.DBD52中,再調(diào)用FC3寫功能,這樣第一個(gè)計(jì)數(shù)器的初始值為200,這里工作號(hào)10的任務(wù)號(hào)是寫第一個(gè)計(jì)數(shù)器的初始值,DB1.DBB0為寫工作號(hào)存入地址,DB1.DBD52為第一個(gè)計(jì)數(shù)器裝載地址區(qū),同樣讀工作號(hào)100為讀前4路,101為讀后4路計(jì)數(shù)器,讀工作號(hào)存入地址為DB1.DBB2。但寫任務(wù)不能循環(huán)寫,只能分時(shí)寫入。

65:如果對(duì)于4-20 mA模擬量輸入模塊來說,小于4 mA后轉(zhuǎn)換的數(shù)字量是多少?
如果小于4ma,那么將會(huì)是輸出負(fù)值,例如 -1對(duì)應(yīng)的是3.9995mA,而1.185 mA 時(shí),這個(gè)數(shù)值是-4864 (10進(jìn)制)但是如果小于1.185mA,如果禁止斷線檢測(cè),這個(gè)值是8000(16進(jìn)制)如果有斷線檢測(cè),會(huì)變成7FFF(16進(jìn)制)。

66:怎樣對(duì)模擬量進(jìn)行標(biāo)準(zhǔn)化和非標(biāo)準(zhǔn)化?
可以使用以下功能塊:
1.在塊FC164中,x和y都是整數(shù)。
2. FC165中x是整數(shù),y是實(shí)數(shù)。
3. FC166中x是實(shí)數(shù),y是整數(shù)。
4. FC167中x和y都是實(shí)數(shù)。

67:S7系列PLC之間最經(jīng)濟(jì)的通訊方式是什么?
MPI通訊是S7系列PLC之間一種最經(jīng)濟(jì)、數(shù)據(jù)量最小的一種通訊,需要做連接配置的站通過GD通訊,GD通訊適合于S7-300之間,S7-300、S7-400、MPI之間一些固定數(shù)據(jù)的通訊。不用作連接的MPI通訊適用于S7-300之間、S7-300與400之間、S7-300/400與S7-200 系列PLC之間的通訊,建議在OB35(循環(huán)中斷100ms)中調(diào)用發(fā)送塊,在OB1(主循環(huán)組織塊)調(diào)用接收塊。

68:整個(gè)系統(tǒng)掉電后,為什么CPU在電源恢復(fù)后仍保持在停止?fàn)顟B(tài)?
整個(gè)系統(tǒng)由一個(gè)DP主站S7-300/400以及從站組成。而從站通過一個(gè)主開關(guān)被切斷了電源。由于內(nèi)部的CPU電壓緩沖器,CPU 仍繼續(xù)運(yùn)行大約50ms到100ms。此階段里 CPU 識(shí)別出所連接的從站的故障。如果沒有編程OB86和OB122的話,CPU 就會(huì)因?yàn)檫@些有故障的從站而繼續(xù)保留在停止?fàn)顟B(tài)。

69:在點(diǎn)到點(diǎn)通信中,協(xié)議 3964(R)和RK 512 之間的區(qū)別是什么?
這兩個(gè)協(xié)議的主要區(qū)別在于消息報(bào)頭和響應(yīng)消息的不同。使用RK 512,提供有最高的數(shù)據(jù)完整性,程序 3964(R) 當(dāng)傳送信息數(shù)據(jù)時(shí),程序3964(R)將控制字符(安全層)添加到信息數(shù)據(jù)上。這些控制字符激活通信伙伴,檢查數(shù)據(jù)是否全部接收,是否無錯(cuò)誤。

70:當(dāng)一個(gè)DP從站出故障,如何在輸入的過程映像被清成“0”以前保存它們?
當(dāng)一個(gè)DP從站出故障時(shí),OB86(通過S7-300/400)被調(diào)用。可用下列方法“保存”輸入的過程映像:
1. 把從站的所有輸入循環(huán)地復(fù)制到一個(gè)獨(dú)立的區(qū)里。
2.如果從站出問題,則 OB86 被啟動(dòng)。在此 OB 里你可設(shè)一個(gè)標(biāo)志位來可防止進(jìn)一步的循環(huán)復(fù)制操作。
3. 當(dāng)從站返回總線后,你把 OB86 里的標(biāo)志位復(fù)位。71:對(duì)模擬量模塊而言,如何處理未使用的通道?
如果模塊帶有MANA : 短接所有的未使用通道的M-到 MANA ,如果可能,連接MANA 到接地極,把模塊的測(cè)量模式設(shè)置為: 0 - 20/ + -20mA. ,短接未使用的COMP+/COMP-. IC+ / IC-可以保持懸空。
如果模塊不帶有 MANA : 把所有未使用的通道M-連接到使用通道的M-.等在輸入端UCM > 2.5V 時(shí),連接所有未使用的 M-到cpu的接地或系統(tǒng)的接地. 把模塊的測(cè)量模式設(shè)置為: 0 - 20/ + -20mA. ,短接未使用的COMP+/COMP-. IC+ / IC-可以保持懸空。
對(duì)于SM 331-7NF10-0AB0模塊在4通道模式:禁止未用的通道,這些輸入端懸空即可
對(duì)于Ex模塊SM 331-7RD:未使用的通道可以保持懸空72:上位機(jī)與plc進(jìn)行通訊,硬件都需要哪些?
  

73:CP5511/5611 診斷測(cè)試后產(chǎn)生錯(cuò)誤代碼,代碼的含義是什么?
0x0300 Cannot find module:
Please check whether the CP5511 is installed and slotted properly.
Check the interrupt and address assignments. Information on further procedures is available also in the STEP 7 Online Help under "Setting the PG/PC Interface", in the paragraph on "Checking the interrupt and address assignments". More information is also available in the STEP 7 Readme file ("Start > SIMATIC > Product notes"), in section 4.4.1 under "Built-in MPI onboard and the MPI PC module -> Setting interrupts and addresses".

0x0312 Incorrect configuration parameters:
Deinstall the CP5511 and reinstall it again. For this you click the "Select" button in the PG/PC interface (Fig. 1). Mark the CP5511 with the cursor in the right window (Fig. 3). Then click the "Deinstall" button. Now, (after restarting STEP 7) you can mark the CP5511 in the left window and click the "Install" button. For this activity you need to have administrator rights to your PC (see STEP 7 Readme file, section 3.1).

0x0313 Baud rate does not correspond with network or incorrect interrupt:
Check the transfer speed (Baud rate) in the PG/PC interface and in the hardware configuration. The Baud rate must not be greater than the Baud rate that is supported by the slowest user. The PROFIBUS addresses configured in the hardware configuration must match the addresses of the system configuration.
Check the interrupt and address assignments. Information on further procedures is available in the STEP 7 Online Help under "Setting the PG/PC interface", in the paragraph on "Checking the interrupt and address assignments" (Index: Check interrupt assignment). More information is also available in the STEP 7 Readme file ("Start > SIMATIC > Product notes"), in section 4.4.1 under "Built-in MPI onboard and the MPI PC module -> Setting interrupts and addresses".

0x0316 Hardware ressource already busy:
If this error message occurs after the installation of the CP5511 in "Setting PG-PC interface

0x031a Cannot find any active PB/MPI network:
Activate the function "PG/PC is the only master on the bus" in the Properties of the PG/PC interface (see Fig. 4). This disables an additional safety function against bus faults. You get to this mask via the "Properties" button - see Fig. 1. The requirement is that the interface parameters used are set to "CP5511(MPI)".

0x0318 Interrupt occupied:
This message appears in most cases in Windows NT. In the BIOS of your computer change the "PnP" setting to "No". You get to the BIOS of your computer by restarting your PC and hitting the F2 key.

0x031b Synchronization error:
Please check the bus parameters on the bus. These must match the bus parameters configured in the hardware configuration.
Check the installation of the bus cable.

0x031c AMPRO2 system error:
Activate the function "PG/PC is the only master on the bus" in the Properties of the PG/PC interface (see Fig. 4).
Please check whether all the terminators for the PROFIBUS network are connected properly.
It is also possible that the STEP 7 drivers are not installed or have been deleted or that an incorrect driver has been installed. In this case we recommend sending the CITAMIS.str file to Customer Support for checking.
Another possible cause might be that the hardware is defective.

0x0320 Cannot find DLL/VXD as file:
On your PC please find the file specified in the Windows Explorer via "Tools > Find > Files/Folders". Either the file is not on your computer or it is found twice. Please rename the file in the Windows system directory and then restart Windows.
In the Registry, the references to the files are missing. Access to the required parameters from the Registry is not possible. Perhaps you don't have the required access rights or the system database is damaged.
The drivers are not compatible with the operating systems.


73:哪些軟件里含有CP5511,CP5512,CP5611,RS232 PC-Adapter 的驅(qū)動(dòng)?
如果安裝了相應(yīng)的軟件后包含“Set PG/PC Interface …”組件,那么這些軟件都含有CP5511,CP5512,CP5611,RS232 PC-Adapter 的驅(qū)動(dòng),只需在“Set PG/PC Interface …”->“Select…”->選擇相應(yīng)的驅(qū)動(dòng),然后“Install-->”即可。
   具體的軟件有Step7,Step7 MicroWin,Simatic Net,WinCC,Protool,F(xiàn)lexible,PCS7。

74:當(dāng)試圖通過TeleService建立PRODAVE MPI和樣列程序之間的通訊時(shí),為什么會(huì)出現(xiàn)出錯(cuò)消息4501?
調(diào)制解調(diào)器沒有響應(yīng),并產(chǎn)生了出錯(cuò)消息4501。在這個(gè)情況下,工作站的規(guī)范不正確。在TeleService對(duì)話框中檢查工作站的名稱和工作站(standort)規(guī)范。此處可能有個(gè)不正確的缺省設(shè)刪除“station”(“standort”)域中的缺省名,或輸入正確的工作站名。那么就可以使用調(diào)制解調(diào)器在PRODAVE MPIY和TeleService之間建立連接。

75:是否可以將數(shù)據(jù)塊的當(dāng)前值作為初始值從AS傳送到項(xiàng)目中?
可以。從AS中“ONLINE,打開相關(guān)數(shù)據(jù)塊(DB).使用軟盤圖標(biāo)“OFFLINE”保存DB.
   通過“File > Generate Source”在DB中產(chǎn)生STL源代碼. 通過手動(dòng)操作將BEGIN和END_DATA_BLOCK行之間的當(dāng)前值與相應(yīng)的聲明(初始值)逐行連接起來,從而得到下列聲明語句:

STRUCT
wordVar : WORD := W#16#ABCD;
...
END_STRUCT ;
編譯STL源代碼。

76:在通訊任務(wù)中,在哪些OB中必須調(diào)用SFB?
在啟動(dòng)型OB(如用于S7-300的OB100和用于S7-400的OB100和OB101)和循環(huán)模式OB(OB1)中,必須調(diào)用數(shù)據(jù)通訊或程序管理(把PLC切換到STOP或RUN)所需的所有SFB。OB100是啟動(dòng)型OB,并在重新啟動(dòng)CPU時(shí)運(yùn)行。例如,在該OB中,用標(biāo)記M1.0和M0.1來釋放第一個(gè)通訊觸發(fā)器。

77:怎樣編程間接訪問一個(gè)ARRAY類型變量的元素?
一個(gè)位、字節(jié)或者字符域的尺寸是按照字節(jié)限制排列的——在所有其它情況下是按照字對(duì)齊的。表T6-1中給出了一個(gè)域的存儲(chǔ)示例。操作系統(tǒng)計(jì)算域中單個(gè)元素末端位置的位地址。域被分配到從下一個(gè)字地址(或字節(jié)地址)。下一個(gè)數(shù)據(jù)類型從下一個(gè)整字開始(或者整字節(jié)).
   聲明部分:
   在聲明部分,必須定義一個(gè)與將被間接尋址的ARRAY有著同一結(jié)構(gòu)的ARRAY。不一定非要將ARRAY聲明為IN-OUT變量;也可以聲明為TEMP、IN或OUT變量。
   網(wǎng)絡(luò):
   域?qū)挾?OFFSET)在網(wǎng)絡(luò)中定義。ARRAY中的單個(gè)元素的最小常規(guī)數(shù)據(jù)寬度是一個(gè)字節(jié);即使在兩個(gè)變量之間定義一個(gè)BOOL。有必要確定相關(guān)的域的寬度和確定下一個(gè)期望域的起始地址。可使用下面的算法:地址(指數(shù)):b = 元素長(zhǎng)度*(指數(shù) - 1)
   創(chuàng)建具有不同數(shù)據(jù)類型的結(jié)構(gòu)時(shí),必須注意,在特定的環(huán)境下可能會(huì)自動(dòng)插入填充字節(jié)。
   保存ARRAY數(shù)據(jù)類型
   示例:ARRAY [1..2,1..3] OF 整數(shù)將生成下列域:
   多維域是按照順序保存的。在本例中整數(shù) [1,1]后面是整數(shù) [1,2],整數(shù) [1,3]后面是整數(shù)[2,1]。

78:STEP 7 以哪種格式存儲(chǔ)POINTER參數(shù)類型?
STEP 7以 6 個(gè)字節(jié)保存POINTER參數(shù)。表4-1顯示了用于保存POINTER參數(shù)類型的內(nèi)存區(qū)域以及每個(gè)字節(jié)中保存的數(shù)據(jù)。POINTER參數(shù)類型保存了下列信息:DB號(hào)(如果DB中沒有保存任何數(shù)據(jù)時(shí)為0)。CPU中的內(nèi)存區(qū)域(表格中列出了不同內(nèi)存區(qū)域的十六進(jìn)制代碼)。
   數(shù)據(jù)的地址(按照Byte.Bit格式)。
如果將形式參數(shù)聲明為POINTER參數(shù)類型,則只需要指定內(nèi)存區(qū)域和地址。STEP 7自動(dòng)將輸入項(xiàng)目的格式轉(zhuǎn)換為指針格式。

79:因?yàn)榭偸且状握{(diào)用Alarm8P(SFB35)塊,怎樣避免OB 1初始化過程花費(fèi)太長(zhǎng)時(shí)間?
激活(首次調(diào)用)報(bào)警塊Alarm(SFB33)、A larm_8(SFB34)和Alarm_8P(SFB35)比簡(jiǎn)單地執(zhí)行作業(yè)檢查需要多花費(fèi) 2 到 3 倍的運(yùn)行時(shí)間。當(dāng)傳送告警時(shí),塊的運(yùn)行時(shí)間也會(huì)同樣長(zhǎng)。然而警報(bào)通常不會(huì)成群發(fā)生,當(dāng)編程時(shí),需要注意警報(bào)塊的首次調(diào)用,因?yàn)榇颂幱玫降乃袎K需要很長(zhǎng)的運(yùn)行時(shí)間,因此被調(diào)用OB的運(yùn)行時(shí)間在某些情況下將顯著增加。將警報(bào)塊的首次調(diào)用移動(dòng)到OB 100/101/102,可以將較長(zhǎng)的運(yùn)行時(shí)間轉(zhuǎn)換到啟動(dòng)過程。此處處理時(shí)間也會(huì)較長(zhǎng),但是由于與模塊的參數(shù)設(shè)置同時(shí)進(jìn)行,啟動(dòng)時(shí)間不會(huì)太長(zhǎng)。

80:當(dāng)不能卸載STEP 7時(shí),該怎么辦?
設(shè)法通過控制面板卸載STEP 7。如果安裝文件已損壞,卸載程序常會(huì)出錯(cuò),并伴隨出錯(cuò)信息。另外STEP 7 CD包含文件Simatic STEP7.msi。可以通過這個(gè)文件卸載STEP 7。81:加密的300PLC MMC處理方法
如果您忘記了您在S7-300CPU Protection屬性中所設(shè)定的密碼,那么您只能夠采用siemens的編程器PG(6ES7798-0BA00-0XA0)上的讀卡槽或采用帶USB接口的讀卡器(USB deleteàS7 Memory Cardàprommer 6ES7792-0AA00-0XA0),選擇SIMATIC Manager界面下的菜單 File 選項(xiàng)刪除MMC卡上原有的內(nèi)容,這樣MMC就可以作為一個(gè)未加密的空卡使用了,但無法對(duì)MMC卡進(jìn)行jie密,讀取MMC卡中的程序或數(shù)據(jù)。

文章版權(quán)歸西部工控xbgk所有,未經(jīng)許可不得轉(zhuǎn)載。

主站蜘蛛池模板: 免费不卡视频 | 在线国产一区二区 | 国产成人精品免费视频大全最热 | 欧美日韩精品一区二区 | 国产1区2区3区在线观看 | 国产曰批免费观看久久久 | 国产精品九九 | 日韩电影免费观 | 亚洲精品视频一区二区三区 | 综合久久亚洲 | 亚洲国产精品成人久久久 | 国产一区二区在线免费视频 | 久久精品一区二区国产 | 91久久久久久久久久久久久 | 亚洲一区二区视频在线观看 | 在线观看成人av | 黄色短视频在线播放 | 亚洲最大av网 | 黄色小视频在线 | 麻豆成人av | 国产成人精品a视频一区www | 国产真乱mangent | 成年人视频免费在线观看 | 国产精品国产三级国产 | 欧美精品网站 | 午夜视频在线免费 | 麻豆国产原创 | 欧美精品久久久久a | 香蕉午夜 | 一区二区三区欧美日韩 | 欧美专区一区二区三区 | 亚洲三级免费 | 国产在线网站 | 国产精品66| 激情欧美日韩 | 3344成人免费高清免费视频 | 成人免费毛片aaaaaa片 | 欧美91视频 | 国产黄a三级三级看三级 | 日韩精品久久久久久久电影99爱 | 亚洲精品久 |